Standards
xEnergy complies with the following international standards 

AS/NZS 61439-1 General rules 

AS/NZS 61439-2 Power switchgear and controlgear assemblies 

IEC/TR 61641 Ed 2.0 Enclosed low-voltage switchgear and controlgear assemblies

Guide for testing under conditions of arcing due to internal fault 

IEC 60529 Degrees of protection (IP Code) 

 

System Busbar Back Busbar Top 

Rated operational voltage 380 - 690 Vac 380 - 690 Vac 

Rated frequency 50 / 60 Hz 50 / 60 Hz
Main busbar data
Position of the bars rear - top/bottom top/center/bottom/vertical
Rated insulation voltage 1000 Vac 1000 Vac
Rated impulse withstand voltage up to 12 kV up to 12 kV
Rated current 800 - 5500 A 800 - 6300 A
Rated short-time withstand current 50 - 100 kA / 1 s and 50 - 66 kA / 3 s 35 - 105 kA / 1 s and 35 - 66 kA / 3 s
Rated peak withstand current 220 kA 220 kA
Vertical distribution busbar data
Rated insulation voltage 1000 Vac 1000 Vac
Rated impulse withstand voltage up to 12 kV up to 12 kV
Application Fixed / Removable / Withdrawable Fixed / Removable / Withdrawable
Rated current 800 - 2000 A 800 - 2000 A
Rated short-time withstand current up to 100 kA / 1 s up to 105 kA / 1 s
Rated peak withstand current 220 kA 231 kA
Enclosure data
Degree of protection IP31 / IP42 / IP55 IP31 / IP42 / IP55

Form of separation Form 2b / Form 3b / Form 4a & 4b Form 2b / Form 3b / Form 4a & 4b
Form 4a type 2 / Form 4b type 6 & 7 Form 4a type 2 / Form 4b type 6 & 7
Entry of cables Top and / or bottom Top and / or bottom
Access Front Front and rear
Standard Colour RAL 7035 / Special colours are available RAL 7035 / Special colours are available

2 1.png

XP Power Section
• Incoming supplies, outgoers and couplings

with circuit breakers IZMX16/40 and Series NZM
• Internal separation up yo form 4
• Cable connection from the top or bottom
• Incoming supply systems for drill-free cable connection
• Fixed or withdrawable
• 3 or 4 pole and 3p+N
• 630 - 6300 A
• Widths of 425 - 1350mm
• Circuit breakers can be places indivdually,

next to each other or on top of each other

(4 per section)

3 1.png

XF outgoing sections for fixed
outgoers up to 630A in Form 2b

• outgoers with circuit breaker PKZ, PKE, NZM, FAZ
• Section height 2000mm, section depth 600 or 800mm
• Cable connection area at the rear or side

• 3 or 4 pole and 3p+N
• IP31, IP42, IP55
• Widths of 425 - 1350mm
• Circuit breakers can be combined with all

accessory components, e.g. with a rotary drive

• Transpararent doors (glass doors) are available

• Dropper bar can be selected from 800 - 2000A

eaton4 1.png
eaton5 1.png
eaton6 1.png
eaton7 1.png
eaton8 1.png

XF outgoing sections for fixed
outgoers up to 630A in Form 4b

• Section widths 600/800/1000/1200mm
• Module widths 600mm
• Cable connection area at the rear or side

• 3 or 4 pole and 3p+N
• IP31, IP42, IP55
• 
Circuit breakers can be combined with all

accessory components, e.g. with a rotary drive

• Transpararent doors (glass doors) are available

• Dropper bar can be selected from 800 - 2000A

• Clear separation of functional areas

XF Box Solution
• Fixed type Motor Starters

• Section widths 600/800/1000/1200mm
• Module widths 600mm
• Cable connection area at the rear or side

• 3 or 4 pole and 3p+N
• IP31, IP42, IP55
• 
Circuit breakers can be combined with all

accessory components, e.g. with a rotary drive

• Dropper bar can be selected from 800 - 1600A

• Clear separation of functional areas

• Can be operated behind the door or with a

door coupling rotary handle

XG General for general equipment to be installed
• Empty sections for individual equipment to be

installed e.g. Power Factor Correction, Large

Variable Speed Drives, plc systems etc.

• Fitting systems for devices for modular installation
• Individual fixed units on a mounting plate 
• Control technology - mounting plates as high

as the section or split ones can be installed

• Section height 2000mm
• Section depth 400/600/800mm
• Section width 425/600/800/1000/1100/1200/1350mm

• IP31, IP42, IP55

• Compatible with installation systems Profi +, EP, IVS, Sasy60i

XR Removable
• Plug-in Motor Starters
• Power outgoers with circuit breakers and strip
type switch-disconnector-fuse, up to 630 A
• Empty modules for individual applications
• Plug-in modules and strip type switchdisconnector-
fuse can be replaced under
live-line working conditions
• Internal separation up to form4 / type7
• Easy maintenance and reduced down times
• Rated current of dropper bar In
= 800-1600A
• IP31 / IP42 / IP55
• Modules adaptable in height
• Each module can be equipped with a separate door

XW outgoing sections
Withdrawable
• Section widths 600/800/1000/1200mm
• 3 or 4-pole
• Rated current of dropper bars In = 1000A-1600A
• IP31, IP42, IP55
• Internal separation up to Form 4b/type 7
• Empty drawers for individual applications
• Easy and uniform handling
• Unambiguous position indicator
• Drawer units available:
o Energy outgoers up to 400A
o Direct on line starters from 0.06 – 132kW
o Reversing starters from 0.06 – 132kW
o Star-Delta starters from 5.5 – 110kW
• Motor starters above 132kW up to 250kW and
MCCB feeders up to 630A are mounted as fixed units.
• SmartWire-DT solutions are available for
automaton and iMCC applications
• Softstarter solutions are integrated

EATONBUSBAR 1.png

Modular, multi-talented
Air circuit breakers and modular circuit breakers can be installed 

above or next to each other in the xEnergy power feild, 

for use as incomers, outgoers or couplings.

Our incoming cubicles can be fitted with measurement modules. 

They also have space for special versions with

up to 4 current transformers per phase (as usual in the Middle East). 

The current transformers are installed on copper terminals, 

connected to the phase conductors. 

In order to provide the best layout for current transformers 

installation, the phase conductors are routed into the

enclosurers at different depths.

EATON10 1.png

Power Distribution with focus 

on footprint reduction to limit 

the need for increased non-revenue 

generating floor space.

EATON11 1.jpg

XF Box solution - A flexible solution

Outgoing feeder panels are just as easy and flexible to configure.
A large number of switching combinations is possible;
MCCB feeders, Motor Starters, Soft Starters and Variable Speed Drives.
Even special confi gurations of MCCBs with remote operator and / or plug-in socket and rotary handle.
The internal separation can be confi gured for Form 4b.
The cable connection compartments are modular in construction.
This has the advantage that no panels or covers obstruct access to the interior of the compartment
during installation and cabling.
In brief: xEnergy Busbar Top provides an easy to install, technically fully-featured
and cost-effective power distribution system which
saves you time and effort during installation and maintenance.

Complies with the IEC/EN 62208 and EN 60529
standards, as well as with AS/NZS 61439-1/-2

bottom of page